Specifications
Explosion Proof – Class I, Div. 1 , Groups B, C, D
LEL General Purpose |
LEL H2 Specific |
H2 PPM Hydrogen |
O2 Oxygen |
H2S Hydrogen Sulfide |
CO Carbon Monoxide |
CH4 Methane IR |
HC Hydrocarbons IR |
CO2 Carbon Dioxide IR |
|
Part # |
65-2405RK |
65-2451RK |
65-2443-500 65-2443-1000 65-2443-2000 |
65-2322RK |
65-2331RK |
65-2336RK |
65-2394RK-CH4 |
65-2394RK-HC |
65-2396RK-02 65-2396RK-03 65-2396RK-05 65-2396RK-10 |
65-2405RK-05 |
65-2451RK-05 |
||||||||
Sensor |
Catalytic |
Metal oxide |
Galvanic cell |
Electrochemical |
Infrared |
||||
Measuring Range |
0-100% LEL |
0-100% LEL (H2 Specific) |
0-500 ppm 0-1000 ppm 0-2000 ppm |
0-25% Vol. |
0-100 ppm |
0-300 ppm |
0-100% LEL |
0 – 5000 ppm 0 – 5% Vol. 0 – 50% Vol. 0 – 100% Vol. |
|
Lower Detectable Limit (LDL) |
2% of full scale |
0.1% Vol. |
2% of full scale |
||||||
Accuracy (whichever is greater) |
± 5% of |
± 10% of full scale |
±0.5% O2 |
± 5% of |
± 5% of |
± 5% of |
|||
Response Time (T-90) |
30 Seconds |
20 Seconds |
45 Seconds |
90 Seconds |
60 Seconds |
90 Seconds |
30 Seconds |
||
Max Current Draw (24VDC) |
70 mA (power wires) 25 mA (signal wires) 3 wires |
25 mA max, 2 wires |
60 mA (power wires) 25 mA (signal wires) 3 wires |
||||||
Life Expectancy |
2 to 3 years with normal exposure to flammable gas |
3-5 years with normal service |
5 years plus with normal service |
2-3 years with normal service |
5 years plus with normal service |
||||
Operating Environment | |||||||||
Location |
Indoor or outdoor. Explosion proof for Class I, Div. 1, Groups B, C, and D. |
||||||||
Temperature |
-40°F to 167°F -40°C to 75°C |
-4°F to 104°F -20°C to 40°C |
-4°F to 113°F -20°C to 45°C |
-40°F to 104°F -40°C to 40°C |
23°F to 104°F -5°C to 40°C |
-40°F to 122°F -40°C to 50°C |
|||
Humidity | 0 – 99% RH, non condensing | ||||||||
Housing | |||||||||
Housing J Box | Cast aluminum explosion proof, optional stainless steel J-box available | ||||||||
Sensor | Stainless steel explosion proof | ||||||||
Controls | |||||||||
Zero | Sets transmitter output to 4 mA with zero output from sensor | ||||||||
Span | Sets transmitter output to proper level when span gas is applied | ||||||||
Output | 4 – 20 mA signal | ||||||||
Operating Voltage |
11 VDC to 30 VDC |
19 VDC to 30 VDC |
19-30VDC (250 OHMS impedance max) |
11 VDC to 30 VDC |
|||||
Approvals |
65-2405RK UL |
65-2451RK UL |
65-2443-500 UL |
CSA NRTL |
C UL US |
||||
65-2405RK-05 |
65-2451RK-05 |
65-2443-500-05 CSA |
|||||||
Controllers | Compatible with the following controllers: Beacon 110, Beacon 200, Beacon 410A, and 800, also PLC and DCS systems | ||||||||
Warranty | One year materials and workmanship |
Toxic Gas Transmitters – Class I, Div. 2
O2 |
H2S |
CO |
Toxics |
CO2 |
|
Part # |
65-2320RK |
65-2330RK |
65-2335RK |
See chart |
65-2397RK-02 65-2397RK-03 65-2397RK-05 65-2397RK-10
|
Sensor |
Galvanic cell |
Electrochemical |
Infrared |
||
Measuring Range |
0-25% Vol. |
0-100 ppm |
0-300 ppm |
See chart |
0 – 5000 ppm 0 – 5% Vol. 0 – 50% Vol. 0 – 100% Vol. |
Lower Detectable Limit (LDL) |
0.1% Vol. |
2% of full scale |
|||
Accuracy
(whichever is greater) |
± 0.5% O2 |
± 5% of |
± 5% of |
± 10% of |
± 5% of |
Response Time (T-90) |
20 Seconds |
45 Seconds |
30 Seconds |
60 Seconds |
30 Seconds |
Max Current Draw (24VDC) |
25 mA max, 2 wires |
60 mA (power wires) 25 mA (signal wires) 3 wires |
|||
Life Expectancy |
2 years normal |
2 to 3 years with normal service |
5 years plus with |
||
Operating Environment | |||||
Location |
Indoor Class I, Div. 2 |
||||
Temperature |
-4°F to 122°F -20°C to 50°C |
14°F to 104°F -10°C to 40°C |
-40°F to 122°F -40°C to 50°C |
||
Humidity |
0 – 99% RH non condensing |
5-95% RH |
0 – 99% RH |
||
Housing | |||||
Housing J-Box | Cast aluminum, explosion-proof | ||||
Sensor | Plastic or aluminum | ||||
Controls | |||||
Zero | Sets transmitter output to 4 mA with zero output from sensor | ||||
Span | Sets transmitter output to 20 mA with full scale output from sensor | ||||
Operating Voltage | 19 VDC to 30 VDC | ||||
Output | 4-20 mA signal | ||||
Controllers | Compatible with the following controllers: Beacon 110, Beacon 200, Beacon 410A, and 800, also PLC and DCS systems | ||||
Warranty | One year materials and workmanship |
S2 Non Explosion Proof Toxic Assemblies |
||||
Part Number With J-Box | Gas | Range | Resolution | Sensor Type |
65-2340RK-NH3 | Ammonia (NH3)* | 0 – 75.0 ppm | 0.1 ppm | ESM -01 |
65-2341-NH3-75 | Ammonia (NH3) | 0 – 75.0 ppm | 0.1 ppm | CT-7 |
65-2341-NH3-1 | Ammonia (NH3) | 0 – 100 ppm | 1 ppm | CT-7 |
65-2341-NH3-2 | Ammonia (NH3) | 0 – 200 ppm | 1 ppm | CT-7 |
65-2341-NH3-5 | Ammonia (NH3) | 0 – 500 ppm | 1 ppm | CT-7 |
65-2340RK-AsH3 | Arsine (AsH3) | 0 – 1.50 ppm | 0.01 ppm | ESM -01 |
65-2341-CL2-3 | Chlorine (Cl2) | 0 – 3.00 ppm | 0.01 ppm | CT-7 |
65-2341-CL2-05 | Chlorine (Cl2) | 0 – 5.00 ppm | 0.02 ppm | CT-7 |
65-2341-CL2-10 | Chlorine (Cl2) | 0 – 10.0 ppm | 0.1 ppm | CT-7 |
65-2341-CLO2-1 | Chlorine Dioxide (ClO2) | 0 – 1.00 ppm | 0.01 ppm | CT-7 |
65-2340RK-HCN | Hydrogen Cyanide (HCN) | 0 – 15.0 ppm | 0.1 ppm | ESM -01 |
65-2340RK-PH3 | Phosphine (PH3) | 0 – 1.00 ppm | 0.01 ppm | ESM -01 |
65-2340RK-SO2 | Sulfur Dioxide (SO2) | 0 – 6.00 ppm | 0.01 ppm | ESM -01 |
S2 Wiring Matrix |
||||
S2 Transmitter | Number of Wires to Controller | Maximum Distance to Controller | ||
18 AWG wire | 16 AWG wire | 14 AWG wire | ||
LEL / IR / CO2 | 3 | 2500 ft. | 5,000 ft. | 8,000 ft. |
Oxygen | 2 | 2500 ft. | 5,000 ft. | 8,000 ft. |
H2S | 2 | 2500 ft. | 5,000 ft. | 8,000 ft. |
CO | 2 | 2500 ft. | 5,000 ft. | 8,000 ft. |
Toxics | 2 | 2500 ft. | 5,000 ft. | 8,000 ft. |
Specifications subject to change without notice.
Made in the USA
Availability: Manufacturer Sourced. Usually available/ships in 3-7 Days.