Specifications
Explosion Proof Class I, Div. 2 , Groups B, C, D
Toxic Gas Transmitters Class I, Div. 2M2A Toxic Transmitter Sensor Ordering Information*Partial pressure sensor for helium (He) applications. Consult factory for details.
Combustibles |
LEL H2 Specific |
O2 Oxygen |
H2S Hydrogen Sulfide |
CO Carbon Monoxide |
CH4 Methane |
HC Hydrocarbons |
CO2 Carbon Dioxide |
|||||
LEL | PPM | |||||||||||
Part# | UL | 65-2640RK | 65-2647RK | 65-2641RK | 65-2643RK-05 | 65-2645RK-05 | 65-2646RK-05 | 65-2649RK-CH4
65-2658RK-CH4 |
65-2649RK-HC | 65-2660RK-02
65-2660RK-03 65-2660RK-05 65-2660RK-10 |
||
CSA | 65-2640RK-05 | 65-2647RK-05 | 65-2641RK-05 | |||||||||
Sensors | Catalytic | Galvanic cell | Electrochemical | Infrared | ||||||||
Measuring Ranges | 0 – 100% LEL | 0 – 9000 ppmCH4 |
0 – 100% LEL |
0 – 25.0% Vol. | 0 – 100 ppm | 0 – 300 ppm | 0 – 100% LEL
0 – 100% Vol. |
0 – 100% LEL | -02 | 0 – 5000 ppm | ||
-03
-05 |
0 – 5% Vol.
0 – 50% Vol. |
|||||||||||
-10 | 0 – 100% Vol. | |||||||||||
Resolution | 1% LEL | 20 ppm | 1% LEL | 0.1% Vol. | 1 ppm | 1% LEL / 1% Vol. | 20 ppm / 0.01% Vol / 0.1% Vol. / 1% Vol. | |||||
Lower Detectable Limit (LDL) | 2% of full scale | 0.1% Vol. | 2% of full scale | |||||||||
Max Current Draw (24VDC) | 160 mA with alarm 1 and alarm 2 active and all relays energized | 125 mA with alarm 1 and alarm 2
active and all relays energized |
160 mA with alarm 1 and alarm 2
active and all relays energized |
|||||||||
Response Time (T-90) | 35 Seconds or less | 90 Seconds or less |
60 Seconds or less |
90 Seconds or less |
30 Seconds or less | |||||||
Life Expectancy | 2 to 3 years with normal service | 3 to 5 years with normal service | 2 to 3 years with normal service | 5 years plus with normal service | ||||||||
Accuracy (which ever is greater) |
± 5% of reading or ± 2% of full scale | ± 0.5% Vol. O2 | ± 5% of reading or ± 2 ppm H2S |
± 5% of reading or ± 5 ppm CO |
± 5% of reading or ± 2 % of full scale | |||||||
Weather Resistant | Patented water repellent sensor coating | |||||||||||
Alarms | ||||||||||||
Alarm Settings | Two fully programmable alarm set points, increasing / decreasing, latching / self-resetting, on delays, off delays, normally energized or de-energized |
|||||||||||
Alarm Indication | Visual LEDs. Alarm 1, Amber; Alarm 2, Red; Fail, Red | |||||||||||
Relays | 5 amp form ‘C’ contacts for alarm 1, alarm 2, and fail | |||||||||||
Physical | ||||||||||||
Dimensions | Height: 8.5” (215 mm), Width: 5.2” (132 mm), Depth: 4.5” (114 mm) | |||||||||||
Display | Alphanumeric OLED display. 8 characters per line; 2 lines for gas concentration readout, plus user-friendly calibration and setup |
|||||||||||
Enclosure | Explosion proof for Class I, Div 1, Groups B, C, D. | |||||||||||
Enclosure Rating | NEMA 4X, explosion proof, watertight, cast aluminum with o-ring seal and epoxy powder coating | |||||||||||
Controls | Magnet used for calibration functions. Calibrates without opening the housing. Internal push-button controls also available for calibration and setup |
|||||||||||
Operating Environment | ||||||||||||
Operating Temperature | -40°F to 167°F
-40°C to 75°C |
-4°F to 113°F
-20°C to 45°C |
-40°F to 104°F
-40°C to 40°C |
23°F to 104°F
-5°C to 40°C |
-40°F to 122°F
-40°C to 50°C |
|||||||
Relative Humidity | 5 – 95% RH non-condensing | |||||||||||
Location | Indoor or outdoor. Explosion proof for Class I, Div. 1, Groups B, C, D. | |||||||||||
Operating Voltage | 10 VDC – 30 VDC | |||||||||||
Outputs | ||||||||||||
Analog | Linear 4-20 mA signal, into 1000 ohms impedance max (24DC), 0 – 500 ohms max (12VDC) corresponding to 0 – full scale | |||||||||||
Digital | Modbus RTU output standard, fully configurable, 2-wire RS-485, 1200 to 19.2k baud | |||||||||||
Approvals | 65-2640RK UL |
65-2641RK
UL |
C CSA US | C UL US | ||||||||
65-2640RK-05 C CSA US |
65-2641RK-05 C CSA US |
|||||||||||
Controllers | Beacon 110, Beacon 200, Beacon 410A, Beacon 800 as well as most DCS / PLC systems | |||||||||||
Warranty | One year material and workmanship | |||||||||||
O2 Oxygen |
H2S Hydrogen Sulfide |
CO Carbon Monoxide |
Toxics See Chart Below | CO2 Carbon Dioxide |
||||||||
Part# | 65-2666RK
*65-2644RK |
65-2662RK | 65-2663RK | See Chart Below | 65-2661RK-02
65-2661RK-03 65-2661RK-05 65-2661RK-10 |
|||||||
Sensors | Galvanic cell | Electrochemical | Infrared | |||||||||
Measuring Ranges | 0-25% Vol. | 0-100 ppm | 0-300 ppm | See Chart Below | -02 | 0 – 5000 ppm | ||||||
-03
-05 |
0 – 5% Vol.
0 – 50% Vol. |
|||||||||||
-10 | 0 – 100% Vol. | |||||||||||
Resolution | 0.1% Vol. | 1 ppm | See Chart Below | 20 ppm / 0.01% Vol. / 0.1% Vol. / 1%Vol. | ||||||||
Lower Detectable Limit (LDL) | 0.1% Vol. | 2% of full scale | ||||||||||
Response Time (T-90) | 35 Seconds or less | 60 Seconds or less | 30 Seconds or less | |||||||||
Max Current Draw (24VDC) | 125 mA with alarm 1 and alarm 2 active and all relays energized | 160 mA with alarm 1 and alarm 2 active and all relays energized | ||||||||||
Life Expectancy | 2 to 3 years with normal service | 5 years plus | ||||||||||
Accuracy (which ever is greater) |
± 0.5% Vol. O2 | ± 5% of reading or ± 2 ppm H2S |
± 5% of reading or ± 5 ppm CO |
± 10% of reading or ± 5% of full scale |
± 5% of reading or ± 2% of full scale |
|||||||
Alarms | ||||||||||||
Alarm Settings | Two fully programmable alarm set points, increasing / decreasing, latching / self-resetting, on delays, off delays, normally energized or de-energized, | |||||||||||
Alarm Indication | Visual LEDs. Alarm 1=Amber; Alarm 2=Red; Fail=Red | |||||||||||
Relays | 5 Amp form ‘C’ contacts for alarm 1, alarm 2, and fail | |||||||||||
Physical | ||||||||||||
Dimensions | Height: 8.5” (215 mm), Width: 5.2” (132 mm), Depth: 4.5” (114 mm) | |||||||||||
Display | Alphanumeric OLED display. 8 characters per line; 2 lines for gas concentration readout, plus user-friendly calibration and setup | |||||||||||
Sensor Rating | Non explosion proof construction, designed for Class I, Div. 2, Groups B, C, D (no certification) | |||||||||||
Housing J-Box | NEMA 4X, explosion proof, watertight, cast aluminum with o-ring seal and epoxy powder coating | |||||||||||
Controls | Magnet used for calibration functions. Calibrates without opening the housing. Internal push-button controls also available for calibration and setup | |||||||||||
Sensor | Aluminum / Plastic (non explosion proof) | |||||||||||
Operating Environment | ||||||||||||
Operating Temperature | -4°F to 113°F
-20°C to 45°C |
-40°F to 104°F
-40°C to 40°C |
23°F to 104°F
-5°C to 40°C |
14°F to 104°F
-10°C to 40°C |
-40°F to 122°F
-40°C to 50°C |
|||||||
Relative Humidity | 5 – 95% RH non-condensing | |||||||||||
Location | Indoor or outdoor | |||||||||||
Operating Voltage | 10 VDC – 30 VDC | |||||||||||
Outputs | ||||||||||||
Analog | Linear 4-20 mA signal, into 1000 ohms impedance max (24DC), 0 – 500 ohms max (12VDC) corresponding to 0 – full scale | |||||||||||
Digital | Modbus RTU output standard, fully configurable, 2-wire RS-485, 1200 to 19.2k baud | |||||||||||
Controllers | Beacon 110, Beacon 200, Beacon 410A, Beacon 800 as well as most DCS / PLC systems | |||||||||||
Warranty | One year materials and workmanship | |||||||||||
|
Part Number With J-Box | Gas | Range | Resolution | Sensor Type | |||||||
65-2670RK-NH3-75 | Ammonia (NH3) | 0 – 75.0 ppm | 0.1 ppm | CT-7 | ||||||||
65-2670-NH3-1 | Ammonia (NH3) | 0 – 100 ppm | 1 ppm | CT-7 | ||||||||
65-2670-NH3-2 | Ammonia (NH3) | 0 – 200 ppm | 1 ppm | CT-7 | ||||||||
65-2670-NH3-5 | Ammonia (NH3) | 0 – 500 ppm | 1 ppm | CT-7 | ||||||||
65-2648RK-AsH3 | Arsine (AsH3) | 0 – 1.50 ppm | 0.1 ppm | ESM -01 | ||||||||
65-2670RK-CL2-3 | Chlorine (Cl2) | 0 – 3.00 ppm | 0.01 ppm | CT-7 | ||||||||
65-2670RK-CL2-10 | Chlorine (Cl2) | 0 – 10.0 ppm | 0.1 ppm | CT-7 | ||||||||
65-2670RK-CLO2 | Chlorine Dioxide (ClO2) | 0 – 1.00 ppm | 0.01 ppm | CT-7 | ||||||||
65-2648RK-HCN | Hydrogen Cyanide (HCN) | 0 – 15.0 ppm | 0.1 ppm | ESM -01 | ||||||||
65-2648RK-PH3 | Phosphine (PH3) | 0 – 1.00 ppm | 0.01 ppm | ESM -01 | ||||||||
65-2648RK-SO2 | Sulfur Dioxide (SO2) | 0 – 6.00 ppm | 0.01 ppm | ESM -01 |