M2A Series by RKI Instruments
In stock
RKI Instruments M2A series stand-alone explosion-proof transmitter: operates as an independent monitor or as part of an integrated system, connecting by analog or digital signal to virtually any controller, PLC or DCS.
Gas options: LEL - H2 Specific, Hydrogen Sulfide (H2S), Hydrocarbons (HC), LEL, Oxygen (O2), Carbon Monoxide (CO), CH4 (0-100% Vol.), CH4 (0-100% LEL), CO2 (0-5.0% Vol.), CO2 (0-50% Vol.), CO2 (0-100% Vol.), CO2 (0-5000 ppm).
Key benefits
- Operates with or without a controller; direct digital readout on OLED cold-temperature display
- Gases: LEL, O2, H2S, CO, CO2 and 100% Vol CH4; toxics NH3, AsH3, Cl2, ClO2, HCN, PH3 and SO2; infrared sensor for combustibles and CO2
- 4-20 mA and digital Modbus outputs standard
- 2 fully programmable alarm relays plus fail relay
- Non-intrusive calibration via magnetic wand; housing need not be opened, so no need to declassify the area; one-person field calibration
- Automatic zero drift correction for more stable readings
- Explosion-proof construction; patented water-repellent sensor cover
- User-friendly push buttons and OLED menus
- Long-life sensors (2+ years typical)
- Sensor construction rated Class I, Div. 1, Groups B, C, D for flammables, CO, H2S, O2 and CO2; Class I, Div. 2 for other toxics
Specifications
| Combustibles | LEL H2 Specific |
O2 Oxygen |
H2S Hydrogen Sulfide |
CO Carbon Monoxide |
CH4 Methane |
HC Hydrocarbons |
CO2 Carbon Dioxide |
|||||
| LEL | PPM | |||||||||||
| Part# | UL | 65-2640RK | 65-2647RK | 65-2641RK | 65-2643RK-05 | 65-2645RK-05 | 65-2646RK-05 | 65-2649RK-CH4 65-2658RK-CH4 | 65-2649RK-HC | 65-2660RK-02 65-2660RK-03 65-2660RK-05 65-2660RK-10 | ||
| CSA | 65-2640RK-05 | 65-2647RK-05 | 65-2641RK-05 | |||||||||
| Sensors | Catalytic | Galvanic cell | Electrochemical | Infrared | ||||||||
| Measuring Ranges | 0 – 100% LEL | 0 – 9000 ppmCH4 |
0 – 100% LEL |
0 – 25.0% Vol. | 0 – 100 ppm | 0 – 300 ppm | 0 – 100% LEL 0 – 100% Vol. | 0 – 100% LEL | -02 | 0 – 5000 ppm | ||
| -03 -05 | 0 – 5% Vol. 0 – 50% Vol. | |||||||||||
| -10 | 0 – 100% Vol. | |||||||||||
| Resolution | 1% LEL | 20 ppm | 1% LEL | 0.1% Vol. | 1 ppm | 1% LEL / 1% Vol. | 20 ppm / 0.01% Vol / 0.1% Vol. / 1% Vol. | |||||
| Lower Detectable Limit (LDL) | 2% of full scale | 0.1% Vol. | 2% of full scale | |||||||||
| Max Current Draw (24VDC) | 160 mA with alarm 1 and alarm 2 active and all relays energized | 125 mA with alarm 1 and alarm 2 active and all relays energized | 160 mA with alarm 1 and alarm 2 active and all relays energized | |||||||||
| Response Time (T-90) | 35 Seconds or less | 90 Seconds or less |
60 Seconds or less |
90 Seconds or less |
30 Seconds or less | |||||||
| Life Expectancy | 2 to 3 years with normal service | 3 to 5 years with normal service | 2 to 3 years with normal service | 5 years plus with normal service | ||||||||
| Accuracy (which ever is greater) |
± 5% of reading or ± 2% of full scale | ± 0.5% Vol. O2 | ± 5% of reading or ± 2 ppm H2S |
± 5% of reading or ± 5 ppm CO |
± 5% of reading or ± 2 % of full scale | |||||||
| Weather Resistant | Patented water repellent sensor coating | |||||||||||
| Alarms | ||||||||||||
| Alarm Settings | Two fully programmable alarm set points, increasing / decreasing, latching / self-resetting, on delays, off delays, normally energized or de-energized |
|||||||||||
| Alarm Indication | Visual LEDs. Alarm 1, Amber; Alarm 2, Red; Fail, Red | |||||||||||
| Relays | 5 amp form ‘C’ contacts for alarm 1, alarm 2, and fail | |||||||||||
| Physical | ||||||||||||
| Dimensions | Height: 8.5” (215 mm), Width: 5.2” (132 mm), Depth: 4.5” (114 mm) | |||||||||||
| Display | Alphanumeric OLED display. 8 characters per line; 2 lines for gas concentration readout, plus user-friendly calibration and setup |
|||||||||||
| Enclosure | Explosion proof for Class I, Div 1, Groups B, C, D. | |||||||||||
| Enclosure Rating | NEMA 4X, explosion proof, watertight, cast aluminum with o-ring seal and epoxy powder coating | |||||||||||
| Controls | Magnet used for calibration functions. Calibrates without opening the housing. Internal push-button controls also available for calibration and setup |
|||||||||||
| Operating Environment | ||||||||||||
| Operating Temperature | -40°F to 167°F -40°C to 75°C | -4°F to 113°F -20°C to 45°C | -40°F to 104°F -40°C to 40°C | 23°F to 104°F -5°C to 40°C | -40°F to 122°F -40°C to 50°C | |||||||
| Relative Humidity | 5 – 95% RH non-condensing | |||||||||||
| Location | Indoor or outdoor. Explosion proof for Class I, Div. 1, Groups B, C, D. | |||||||||||
| Operating Voltage | 10 VDC – 30 VDC | |||||||||||
| Outputs | ||||||||||||
| Analog | Linear 4-20 mA signal, into 1000 ohms impedance max (24DC), 0 – 500 ohms max (12VDC) corresponding to 0 – full scale | |||||||||||
| Digital | Modbus RTU output standard, fully configurable, 2-wire RS-485, 1200 to 19.2k baud | |||||||||||
| Approvals | 65-2640RK UL |
65-2641RK UL | C CSA US | C UL US | ||||||||
| 65-2640RK-05 C CSA US |
65-2641RK-05 C CSA US |
|||||||||||
| Controllers | Beacon 110, Beacon 200, Beacon 410A, Beacon 800 as well as most DCS / PLC systems | |||||||||||
| Warranty | One year material and workmanship | |||||||||||
| O2 Oxygen |
H2S Hydrogen Sulfide |
CO Carbon Monoxide |
Toxics See Chart Below | CO2 Carbon Dioxide |
||||||||
| Part# | 65-2666RK *65-2644RK | 65-2662RK | 65-2663RK | See Chart Below | 65-2661RK-02 65-2661RK-03 65-2661RK-05 65-2661RK-10 | |||||||
| Sensors | Galvanic cell | Electrochemical | Infrared | |||||||||
| Measuring Ranges | 0-25% Vol. | 0-100 ppm | 0-300 ppm | See Chart Below | -02 | 0 – 5000 ppm | ||||||
| -03 -05 | 0 – 5% Vol. 0 – 50% Vol. | |||||||||||
| -10 | 0 – 100% Vol. | |||||||||||
| Resolution | 0.1% Vol. | 1 ppm | See Chart Below | 20 ppm / 0.01% Vol. / 0.1% Vol. / 1%Vol. | ||||||||
| Lower Detectable Limit (LDL) | 0.1% Vol. | 2% of full scale | ||||||||||
| Response Time (T-90) | 35 Seconds or less | 60 Seconds or less | 30 Seconds or less | |||||||||
| Max Current Draw (24VDC) | 125 mA with alarm 1 and alarm 2 active and all relays energized | 160 mA with alarm 1 and alarm 2 active and all relays energized | ||||||||||
| Life Expectancy | 2 to 3 years with normal service | 5 years plus | ||||||||||
| Accuracy (which ever is greater) |
± 0.5% Vol. O2 | ± 5% of reading or ± 2 ppm H2S |
± 5% of reading or ± 5 ppm CO |
± 10% of reading or ± 5% of full scale |
± 5% of reading or ± 2% of full scale |
|||||||
| Alarms | ||||||||||||
| Alarm Settings | Two fully programmable alarm set points, increasing / decreasing, latching / self-resetting, on delays, off delays, normally energized or de-energized, | |||||||||||
| Alarm Indication | Visual LEDs. Alarm 1=Amber; Alarm 2=Red; Fail=Red | |||||||||||
| Relays | 5 Amp form ‘C’ contacts for alarm 1, alarm 2, and fail | |||||||||||
| Physical | ||||||||||||
| Dimensions | Height: 8.5” (215 mm), Width: 5.2” (132 mm), Depth: 4.5” (114 mm) | |||||||||||
| Display | Alphanumeric OLED display. 8 characters per line; 2 lines for gas concentration readout, plus user-friendly calibration and setup | |||||||||||
| Sensor Rating | Non explosion proof construction, designed for Class I, Div. 2, Groups B, C, D (no certification) | |||||||||||
| Housing J-Box | NEMA 4X, explosion proof, watertight, cast aluminum with o-ring seal and epoxy powder coating | |||||||||||
| Controls | Magnet used for calibration functions. Calibrates without opening the housing. Internal push-button controls also available for calibration and setup | |||||||||||
| Sensor | Aluminum / Plastic (non explosion proof) | |||||||||||
| Operating Environment | ||||||||||||
| Operating Temperature | -4°F to 113°F -20°C to 45°C | -40°F to 104°F -40°C to 40°C | 23°F to 104°F -5°C to 40°C | 14°F to 104°F -10°C to 40°C | -40°F to 122°F -40°C to 50°C | |||||||
| Relative Humidity | 5 – 95% RH non-condensing | |||||||||||
| Location | Indoor or outdoor | |||||||||||
| Operating Voltage | 10 VDC – 30 VDC | |||||||||||
| Outputs | ||||||||||||
| Analog | Linear 4-20 mA signal, into 1000 ohms impedance max (24DC), 0 – 500 ohms max (12VDC) corresponding to 0 – full scale | |||||||||||
| Digital | Modbus RTU output standard, fully configurable, 2-wire RS-485, 1200 to 19.2k baud | |||||||||||
| Controllers | Beacon 110, Beacon 200, Beacon 410A, Beacon 800 as well as most DCS / PLC systems | |||||||||||
| Warranty | One year materials and workmanship | |||||||||||
| Part Number With J-Box | Gas | Range | Resolution | Sensor Type | ||||||||
| 65-2670RK-NH3-75 | Ammonia (NH3) | 0 – 75.0 ppm | 0.1 ppm | CT-7 | ||||||||
| 65-2670-NH3-1 | Ammonia (NH3) | 0 – 100 ppm | 1 ppm | CT-7 | ||||||||
| 65-2670-NH3-2 | Ammonia (NH3) | 0 – 200 ppm | 1 ppm | CT-7 | ||||||||
| 65-2670-NH3-5 | Ammonia (NH3) | 0 – 500 ppm | 1 ppm | CT-7 | ||||||||
| 65-2648RK-AsH3 | Arsine (AsH3) | 0 – 1.50 ppm | 0.1 ppm | ESM -01 | ||||||||
| 65-2670RK-CL2-3 | Chlorine (Cl2) | 0 – 3.00 ppm | 0.01 ppm | CT-7 | ||||||||
| 65-2670RK-CL2-10 | Chlorine (Cl2) | 0 – 10.0 ppm | 0.1 ppm | CT-7 | ||||||||
| 65-2670RK-CLO2 | Chlorine Dioxide (ClO2) | 0 – 1.00 ppm | 0.01 ppm | CT-7 | ||||||||
| 65-2648RK-HCN | Hydrogen Cyanide (HCN) | 0 – 15.0 ppm | 0.1 ppm | ESM -01 | ||||||||
| 65-2648RK-PH3 | Phosphine (PH3) | 0 – 1.00 ppm | 0.01 ppm | ESM -01 | ||||||||
| 65-2648RK-SO2 | Sulfur Dioxide (SO2) | 0 – 6.00 ppm | 0.01 ppm | ESM -01 | ||||||||
*Partial pressure sensor for helium (He) applications: consult factory for details.
Product information supplied by the manufacturer (RKI Instruments).
Product codes
- LEL - H2 Specific — SKU: 65-2641RK
- Hydrogen Sulfide (H2S) — SKU: 65-2645RK-05
- Hydrocarbons (HC) — SKU: 65-2649RK-HC
- LEL — SKU: 65-2640RK
- Oxygen (O2) — SKU: 65-2643RK-05
- Carbon Monoxide (CO) — SKU: 65-2646RK-05
- CH4 (0-100% Vol.) — SKU: 65-2658RK-CH4-4
- CH4 (0-100% LEL) — SKU: 65-2649RK-CH4-4
- CO2 (0-5.0% Vol.) — SKU: 65-2660RK-03
- CO2 (0-50% Vol.) — SKU: 65-2660RK-05
- CO2 (0-100% Vol.) — SKU: 65-2660RK-10
- CO2 (0-5000 ppm) — SKU: 65-2660RK-02
Couldn't load pickup availability
Discuss your requirements with Russmill Safety: sales@russmillsafety.com.
Selection & specifications
Selection & specifications
Review the product description, available variants and manufacturer’s specifications before ordering. PPE must be selected for the hazards and requirements of your workplace.
Shipping & returns
Shipping & returns
Review our Shipping Policy and Refund Policy for current terms.
Care & product support
Care & product support
Follow the manufacturer’s care, inspection and replacement instructions. Need clarification? Contact customerservice@russmillsafety.com with the product name or SKU.
Available payment methods are displayed at checkout. Review your order and delivery details before completing payment.
Quick order list
Match equipment to your workplace hazards and the manufacturer’s published specifications. Check sizing, compatible components and intended use before ordering.
Read our Shipping Policy and Refund Policy. Contact our team about product and order requirements.
Send product names or SKUs, quantities, sizes and your destination to sales@russmillsafety.com to discuss your requirements.